Product Description
Siemens 5WG1605-1DB41, N 605D41
-
For control of electrothermal valve drives for AC 24...230 V in heating/cooling systems via 6 noiseless semiconductor outputs
-
Electronic protection of the outputs against short circuit and overload
-
Rated current: 0.5 A per channel and group of 3 outputs
-
Max. inrush current (2 sec.): 3.5 A per channel and group of 3 outputs
-
Max. inrush current (2 min.): 0.9 A per channel and group of 3 outputs
-
Direct operation per channel for opening and closing the valve and activating direct operation
-
Red LED per channel to indicate valve open or closed and status of the control value
-
Red error LED per channel to indicate overload/short circuit and pover voltage failure
-
Maintenance-free terminals for connection and through-wiring of untreated single-core, stranded or multi-core conductors, 0.5 ... 2.5 mm²
-
2 terminals per channel for connecting the electrothermal valve drives
-
2 terminals on the unit for supply of the valve voltage AC 24...230 V
-
Bus-powered electronics
-
Housing: plastic, color RAL 7035, N-system
-
DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715
-
Type of protection: IP 20
Additional functionalities GAMMA
-
Per channel setting of the valve operation direction de-energised open or closed
-
Per channel optional control via switching commands or continuous positioning commands
-
Per channel control value limitation and adjustment of the valve characteristic for continuous control values
-
Per channel control value monitoring
-
Adjustable behaviour in case of override (lock, service mode, forced position, forced control)
-
Per output automatic, demand-oriented or manual valve rinsing
-
Per output operating hours counting and switching cycle counting with limit value monitoring
-
Evaluation of control values for heating or cooling demand requirements on a primary system and for controlling heating or cooling circuit pumps
-
6 room temperature controllers for 2-pipe or 4-pipe systems, adjustable as 2-position control or continuous control, for heating-only mode, cooling-only mode, heating and cooling mode, with two-stage heating or cooling
-
Output of the control values optionally as switching command On/Off or as continuous control command
-
13 min., max. and weighted value calculators
-
6 logical operations (AND/OR/XOR/TRIGGER/LOCK)
-
Surveillance of device function
HS CODE: 85371091
COO: Romania